svenska Login Get Registered Catalog Browser Contact Us
Global expert in cables and cabling system

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

Defrost Gutter

Send link to this page print Your Nexans contact on this page
Defrost Gutter Self limiting cable for roof gutters and drains
Standards
International  Nexans specification
Description

Defrost Gutter is a self-regulating heating cable. Defrost Gutter is ideal for frost protection or temperature maintenance of pipe work and vessels in the construction and refrigeration industries. Defrost Gutter is recommended for frost protection of roof gutters and drains

It can be cut-to-length on site, and exact piping lengths can be mathced without any complicated design considerations.

Its self-regulating characteristics improve safety and reliability. Defrost Gutter wil not overheat or burnout, even when overlapped upon itself. Its power output is self-regulating in responce to the pipe temperature.

The installation of Defrost Gutter is quick and simple and requires no special skills or tools. Termination splicing and power connection components are all provided in convenient kits.


 TOP
Characteristics
Construction characteristics
Conductor flexibility Stranded  
Sheath colour Black  
Conductor material Tinned copper  
Dimensional characteristics
Conductor cross-section 5mm²  
Nominal outer diameter 7.3mm  
Approximate weight 5.9kg/100m  
Electrical characteristics
Operating voltage 230V  
Power 18W  
Resistance of the screen 18.2Ohm/km  
Usage characteristics
Max. temperature energized, outer sheath 35°C  
Output at 5 °C 16W/m  

 TOP
Results   1/1
Select all Items Nexans ref. Country ref. Name
Make to order product 130378 E 8956800 Defrost Gutter
Add to favorites

 TOP
Table for Defrost Gutter

 

 

 

 

Starttemperatur

10 A

16 A

20 A

 + 10 °C

80 m

120 m

150 m

 ± 0 °C

45 m

60 m

80 m

 - 20 °C

30 m

48 m

60 m


 TOP
Defrost Gutter   Defrost Gutter broschyr (1306 kB)
Defrost Gutter   Defrost Gutter Technical information (168 kB)
Defrost Gutter   Bild Gutter och clip (128 kB)

Defrost Gutter Clip