LANmark-OF MPO-MPO Pre-Term Trunk for Singlemode OS2, OM3 and OM4

Tipsa om sidan genom att skicka en länk Skriv ut / Spara Kontaktinformation
LANmark-OF MPO-MPO Pre-Term Trunk for Singlemode OS2, OM3 and OM4
  • Factory terminated MPO-MPO fibre assembly
  • Flexible fan-out for ease of installation in patch panel
  • Small cable diameter reduces required data centre space
  • Polarity in optical channel is easily maintained by its advanced design
  • Only one type of patch cords and one type of cassettes required
  • Fibre count between 12 and 96
  • Strong fibre assembly with pulling eye
  • Fibre type: Singlemode (OS2), OM3 and OM4
  • LANmark-OF MPO and low loss MPO connectivity performance
LANmark-OF
Standarder
Internationell  ISO/IEC 11801:2002/Amd 1:2008/Cor 1:2008
Beskrivning

MPO-MPO Pre-Term characteristics

The Pre-Term is based on an advanced Micro-Bundle design for the cable.  The central strength element and the aramid yarns result in a mechanical strong cable, while the Micro-Bundle allow to reduce the diameter of the cable.

This round cable design facilitates the installation of the MPO-MPO Pre-Term: the small bending radius in any direction eliminates the problems of preferential bending associated with traditional ribbon MPO cables.

The small diameter of 5.4 mm for cables up to 48 fibres and of 6.4 mm for the cable with 96 fibres of the cable reduces significantly the expensive space required for cabling in a data centre and facilitates the airflow. The small diameter also reduced the weight of the cable putting less requirements on the cable trays.

The Pre-Term is delivered with protecting tubes around the installed MPO-connectors and with a pulling eye on one side.  This pulling eye is connected to the internal strength element of the cable. 

The MPO fan-out starts at 50 cm from the cable grand and every next connector is 12 cm further away from the cable gland.  For the 96 core the MPO connectors are grouped by 2 for easy installation in the patch panel and the distance between 2 pairs of MPO connectors is 12 cm.

The Pre-Term is available with OM3, OM4 and singlemode fibres.  The singlemode fibres are according the specifiactions for G652D and OS2 cables.  Details on the fibre specifications can be found in the detailed fibre datasheets.

The typical value for the insertion loss for a normal loss MPO-MPO connection is 0,3 dB. The limit value is 0,6 dB measured according to standard IEC61300-3-45.


The typical value for the insertion loss for a low loss MPO-MPO connection is 0,2 dB. The limit value is 0,35 dB measured according to standard IEC61300-3-45.
 

Polarity in the optical channel during installation is guaranteed due to a pair flip fibre construction.  This is in agreement with standard TIA 568-B-1-7-2006 method C. It allows the continuous use of the standard patch cords eliminating the need to buy optically straight patch cords. Also polarity is maintained with the same type of cassette on both sides of the channel without the need to flip the cassette on one side. 

The MPO-MPO Pre-Term has standard non-pinned (female) connectors. This matches with the pinned (male) connectors in the MPO cassettes.

The Pre-Term meets the requirements for flame non propagation (IEC 60332-1) and fire non-propagation (IEC 60332-3).  The outer jacket of the pre-term is LSZH.

The MPO-MPO Pre-Term are custom made to the required customer length.

 

Consistent quality

 

In order to produce high quality, reliable pre-terminated multi-fibre cables, there are a number of physical characteristics that must be addressed. Therefore, all LANmark-OF MPO-MPO Pre-Term are fully terminated and tested in a quality assured factory environment.   They are delivered with these test results. 


 TOP
Egenskaper
Mekaniska egenskaper
Dragpåkänning, max 1000N  
Kontinuerlig belastning, max 250.0N  
Trycktålighet över en längd av 10 cm 100N/cm  
Tålighet mot mekanisk påkänning 10 impacts of 1 N.m  
Hanteringsinformation
Drifttemperatur, område -10 .. 60°C  
Temperaturområde i lager -20 .. 60°C  
Brandspridningsklass SS 424 14 75 klass F4  
Brandspridningsklass SS 424 14 75 klass F2  

 TOP
Cable Characteristics

Fibre count

12F/24F/48F

96F

Cable Daimeter

5.4 mm

6.4 mm

Cable Weight (kg/km)

31 kg

50 kg

Minimum bending radius during installation

80 mm

100 mm

Minimum bending radius installed

65 mm

65 mm


Insertion loss for individual MPO connection

Fibre type

Multimode (OM3 or OM4)

Singlemode (OS2 with G652D)

Normal loss connection -Typical loss

0.3 dB

0.3 dB

Normal loss connection - Max loss

0.6 dB

0.6 dB

Low loss connection - Typical loss

0.15 dB

0.15 dB

Low loss connection - Max loss

0.35 dB

0.35 dB

Meausured in manufacturing according to standard IEC 61300-3-45

N-number codification: N15A.MKKPVXXX

Letter in N-number

Description

Variations

A

Fibre type

4: SM (OS2) or 5: OM3, 7: OM4

KK

Fibre count

12,24, 48 or 96

P

Performance

Normal (S) or low loss (L)

V

Fanout type

A: pulling eye one side + first MPO at 50 cm + sequential MPO every 12 cm (12, 24 and 48 fibres)

E: pulling eye one side + first 2 MPO at 50 cm + sequential 2 MPO every 12 cm (96 fibres)

XXX

Length between glands

001-300 m

Example: N155.M48LA050: LANmark-OF MPO-MPO Pre-Term with 48 OM3 fibres, low loss connectors, pulling eye on one side, first MPO connector at 50 cm from cable gland and with a length of 50 m between the cable glands