Alsecure Plus 1 kV ≥6 mm2

Send link to this page print Your Nexans contact on this page
Alsecure Plus 1 kV ≥6 mm2 The cable may be used for fixed installation both indoors and outdoors in places that have requirements of function during and after fire i.e. lightings, alarms and control systems. The cable can be installed directly in the ground.
Lifemark
Standards
International  HD 604.5D
Description

Alsecure Plus is a halogen free, flame retardant power cable with circular or sector shaped, annealed, stranded copper conductors. The cable is insulated with Mica tape+coloured XLPE and a screen of annealed copper wires with opposite open helix of copper. Alsecure Plus is designed according to HD 603. The conductors have resistance and number of wires according to IEC 60228 class 2. The cores are identified by colours according to HD 308. The sheath is marked type/manufacturer/year+month/metre marking. Alsecure Plus meets the requirements for flammability IEC 60332-3 category C (F4C) and emits no corrosive gases when burning and has low smoke production. The cable is certified by SEMKO.

 

Lifemark(TM) recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

Certification

Certified by SEMKO.

Fire characteristics

Tested and approved according to several international standards, among others IEC 60331, IEC 60332-3 cat C SS 424 14 75 class F4C IEC 61034, IEC 60754-2 and BBR 94 class EI30. 

Quality system

Designed, manufactured and tested in accordance with ISO 9001.

Environmental management system

The activities at our plant in Grimsås are certified to ISO 14001.

 

REMARK! As a market action we will change from black to orange colour. This mean that we will deliver both black and orange during some time. There is no technical changes, only the colour.
 



Related documents
  Environmental information  (102.4kb)



 TOP
Characteristics
Construction characteristics
Conductor material Aluminium / Polyester tape  
Conductor flexibility Stranded class 2  
Insulation Pole mounted  
Outer sheath HFFR (polyolefin)  
Halogen free PE  
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV  
Usage characteristics
Minimum installation temperature -10°C  
Recommended minimum installation temperature 0°C  
Maximum operating temperature 90°C  
Short-circuit max. conductor temperature 250°C  
Bending factor when laying 12(xD)  
Bending factor when installed 8(xD)  
Fire resistant Yes  
Smoke density IEC 61034  
Fire retardant IEC 60332-3 Cat.C  
Gases corrosivity IEC 60754-2  

 TOP
Your selection
Number of cores  
Conductor cross-section  mm²
Colour  
Nominal outer diameter  mm
Approximate weight  kg/km
Conductor shape  
Apply
Reset
Results   12/12
Select all Items Nexans ref. Country ref. Nb. of cores Cross section (mm²) Colour Nom. outer diam. (mm) Approx. weight (kg/km)
35123998 0055455 4 6 Orange 18.1 551
35124198 0055465 4 10 Orange 22.0 806
35124398 0055475 4 16 Orange 24.2 1155
35124598 0055485 4 25 Orange 26.0 1304
35124798 0055495 4 35 Orange 30.0 2020
35126598 0055505 4 50 Orange 35.0 2700
35125198 0055515 4 70 Orange 36.0 3840
35125398 0055525 4 95 Orange 41.0 4412
35125598 0055535 4 120 Black or orange 42.2 5565
35125798 0055545 4 150 Orange 49.0 6433
35125998 0055555 4 185 Black or orange 52.0 8290
35126198 0055565 4 240 Black 60.0 11050
Add to favorites

 TOP
Selling delivery information
Alsecure Plus will be delivered in lengths of 500 m. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Alsecure Plus 1 kV ≥6 mm2   Environmental information (102 kB)