Alsecure Plus Multicores 300/500 V

Products

Alsecure Plus Multicore 300/500 V 7G1,5

Nexans ref. 27001498-910-05 - Country ref. 0110045

  • Packaging: Drum (m)
  • Number of cores: 7
  • Approximate weight: 23.0 kg/100m
  • Maximum outer diameter: 14.0 mm

 

Alsecure Plus Multicore 300/500 V 12G1,5

Nexans ref. 27001198-910-05 - Country ref. 0110055

  • Packaging: Drum (m)
  • Number of cores: 12
  • Approximate weight: 42.0 kg/100m
  • Maximum outer diameter: 19.5 mm

 

Alsecure Plus Multicore 300/500 V 19G1,5

Nexans ref. 27004198-910-05 - Country ref. 0110065

  • Packaging: Drum (m)
  • Number of cores: 19
  • Approximate weight: 60.0 kg/100m
  • Maximum outer diameter: 22.5 mm

 

Description

Description

Standards

  • National
    NF C32-310

Alsecure Plus Multicores is a halogen free, flame retardant, non-screened control cable with circular, solid copper conductors. The cable is designed according to NF C32-310. The conductors have resistance and number of wires according to IEC 60228 class 1. The insulation is of silicon rubber and the cores are identified by numbers according to HD 308. Alsecure Plus Multicores meets the requirements for flammability IEC 60332-3 category B and emits no corrosive gases when burning and has low smoke production. The cable is fire resistant according to IEC 60331.

 

Installation

ALSECURE PLUS Multicore cables will be installed to the wiring regulation and installation standards in force.

Laying temperature: in case of laying below 0°C, warm up the cable in a heated room 48 hours minimum before installation.

ALSECURE PLUS Multicore cables are not designed for buried installation.

 

Certification

This cable is tested and certified by UTE.

 

Fire characteristics

The cables are tested and approved according to several national and international standards.

  • Fire resistant according to IEC 60331, BBR 94 class El90, NF C 32-070 Cat. CR1, EN 50200, NBN C 30-004 F2 FR2 PH60, BS 6387 cat CWZ
  • Fire retardant according to IEC 60332 Part 2 & 1, SS 424 14 75 min class F4, NF C 32-070 Cat. C1 & C2, EN 50266, NBN C 30-004 F2
  • Low smoke : IEC 61034, NF C 32-073, EN 50268
  • Halogen free : IEC 60754, NF C 32-074, EN 50267

 

Quality and environmental management system

Certified according to ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.

 

Marking

ALSECURE PLUS n (G or x) S mm² 300 V NF C 32-310 CR1/C1 NF-USE 205 F2 FR2 60
n = number of cores
G = with Green/Yellow
x = without Green/Yellow
S = section in mm²

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Round, massive
Insulation
Silicone
Outer sheath
HFFR (polyolefin)
Colour
Orange
Halogen free
Yes
Conductor flexibility
Class 2

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
1.5 mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
300/500 V

Usage characteristics

Usage characteristics

Operating temperature, range
-10 ... 60 °C
Recommended minimum installation temperature
0 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-3 Cat. B
Bending factor when installed
6 (xD)

Resources

Resources

Documentation

Selling & delivery Information

Alsecure Plus Multicores will be delivered in lengths of 500 m. The drum is marked with manufacturer, type of cable and length.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close