Description
NBN 713-020
INFIT Technology
Halogen free
Fire resistant cables
Standards
International : IEC 60228Description
Application
ALSECURE® PREMIUM cables are designed to be used in safety systems (emergency lights, warning systems, fire fighting equipments, etc ...) in all premises open to the public (concert hall, theaters, cinemas, department stores, hospitals, schools, etc ...), in high-rises buildings, in tunnels, in industries.
ALSECURE® PREMIUM cables, with INFIT™ technology, are fire resistant and fire retardant, low smoke and halogen free. In the event of fire, emitted gazes are non corrosive and have a very low toxicity.
Installation
ALSECURE® PREMIUM cables will be installed in accordance with the current regulation. ALSECURE® PREMIUM has to be protected against direct sun lighting when used outside.
In case of laying operation between 0°C and -10°C, warm up the cables in a heated room 48 hours minimum before installation.
ALSECURE® PREMIUM cables are not designed for buried installation.
ALSECURE® PREMIUM products are designed in order to simplify installation conditions thanks to a very high sturdiness of INFIT™ insulation.
Fire performance
- Fire resistant according to :
International : IEC 60331-21, EN 50200, EN 1363 (PH 60),
Belgium : NBN C 30-004 FR2 Rf2h - Fire retardant according to :
International : IEC 60332-3-22/23/24, EN 50266
Belgium : NBN C 30-004 F2
Sweden : SS 424 14 75 class F4A - Flame retardant according to : NF C 32-070-1 Cat C2, IEC 60332-1,
- Low smoke : NF C 32-073, IEC 61034, EN 50268
- Halogen free : NF C 32-074, IEC 60754, EN 50267
- Low toxicity : NF C 20-454 (ITC<5)
- Low corrosivity : NF C 32-074, IEC 60754, EN 50267
Construction
Conductor
Bare copper
Insulation
High mechanical resistance INFIT™ rubber
Outer sheath
Halogen free compound
Colour: orange
Marking
ALSECURE PREMIUM "nx (or G) S" mm2 300/500V NEXANS 279 NBN C 30-004 F2 FR2 Rf2h week year
n = number of cores
S = section in mm²
Characteristics
Construction characteristics | |
---|---|
Conductor material | Bare copper |
Insulation | High mechanical resistance elastomer - INFIT™ in accordance to standard NF C 32 102-1 |
Outer sheath | Halogen free polyolefin |
Sheath colour | Orange |
Higher heating value | 1390MJ/km |
With Green/Yellow core | Yes |
Conductor flexibility | Solid class 1 |
With smaller neutral conductor | No |
Dimensional characteristics | |
Number of cores | 5 |
Conductor cross-section | 1.5mm² |
Minimum outer diameter | 9.3mm |
Maximum outer diameter | 10.2mm |
Approximate weight | 170kg/km |
Electrical characteristics | |
Permissible current rating in open air | 23A |
Voltage drop, 3 conductors | 21.5V/A.km |
Rated Voltage Uo/U (Um) | 300 / 500 V |
Mechanical characteristics | |
Cable flexibility | Rigid |
Usage characteristics | |
Fire resistant | IEC 60331-21, EN 1363, NBN C 30-004 FR2 Rf2h |
Fire retardant | IEC 60332-3, EN 1363, NBN C 30-004 F2, SS 424 14 75 class F4A |
Smoke density | IEC 61034 |
Gases toxicity | Low |
Operating temperature, range | -20 .. 60°C |
Flame retardant | IEC 60332-1 |
Max. conductor temperature in service | 90°C |
Docs and info
-
COMPLEMENTARY CHARACTERISTICS
Core identification
(In accordance with european harmonization HD308 S2)
2x: brown - blue
3x: brown - black - grey
3G: brown - blue - green/yellow
4x: brown - black - grey - blue
4G: brown - black - grey - green/yellow
5x: black cores with printed numbers
5G: blue - brown - black - grey - green/yellowType approval
ISSEP : Institut Scientifique de Service Public
Current rating capacities
The data are indicated for continuous duty operation and apply to:
- Maximum conductor temperature = 90 °C
- Nominal frequency = 50 Hz
- One cable in free air (on perforated trays)
- Ambient temperature = 30 °C
Data recording from IEC 60364-5-52 or NF C 15-100
Voltage drop
The data are based on Cos phi = 0.8
Minimum bending radius
r = 6 x cable outer diameter