AXQJ TT 24 kV 1x95/25

Description

Description

Standards

  • International
    HD 620.10K
  • National
    SS 424 14 16

Design

  1. Conductor Circular, stranded aluminium conductor with resistance and number of wires according to SS 424 14 08. The conductor is longitudinally water blocked according to SS 424 14 17.
  2. Inner conducting layer Semiconducting crosslinked polyeten.
  3. Insulation Crosslinked dry cured polyeten (PEX).
  4. Outer conducting layer Crosslinked strippable conducting elastomer.
  5. Screen One layer of circular annealed copper wires, locked with swelltape.
  6. Moisturebarrier sheath Alongrunning plasticcoated aluminiumtape applied with glued overlap. The tape adheres the outher sheath.
  7. Sheath Black HFFR polyolefin. The sheath is marked, ie: "NEXANS NS AXQJ TT 12 kV 1 x 240/35 year month" + metremarking.

Lifemark(TM) recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

Standards

The cable is in appliable parts constructed according to HD 620.5-K. The cable can be loaded according to SS 424 14 16.

Quality system

Designed, manufactured and tested in accordance with ISO 9001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor shape
Round, stranded
Insulation
XLPE (chemical)
Outer sheath
HFFR (Halogene Free Flame Retardant)
Colour
Black
Halogen free
Yes
Conductor flexibility
Class 2
Conductor material
Aluminum
Screen
Copper wires

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Approximate weight
97.0 kg/100m
Average insulation thickness
5.5 mm
Average sheath thickness
1.9 mm
Conductor cross-section
95 mm²
Conductor diameter
11.3 mm
Diameter over insulation
25.1 mm
Nominal outer diameter
32.0 mm
Screen section
25 mm²

Electrical characteristics

Electrical characteristics

Approx. inductance, flat formation
0.64 mH/km
Approx. inductance, trefoil formation
0.38 mH/km
Earth leakage current at 20 kV
2.39 A/km
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Nominal phase capacitance
0.2 µF / km
Operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Resistance of the screen
0.8 Ohm/km

Mechanical characteristics

Mechanical characteristics

Permissible pulling forces
0.03 kN/mm²

Usage characteristics

Usage characteristics

Minimum installation temperature
-10 °C
Recommended minimum installation temperature
0 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Water proof
Longitudinal & radial
Bending factor when installed
10 (xD)
Bending factor when laying
15 (xD)
Length
500 m
Packaging
-
U.V resistance
Yes

Resources

Resources

Selling & delivery Information

The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Declaration of Performance

  • Declaration of Performance n� : 1000167-SEGR
  • Certification Date : 2/19/19
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Dca-s2,d2,a2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close